The V30 CJC™ VACUUM FILTER is designed to remove moisture,
oxygen and other gases from transformer oil. The PLC control of
the unit provides highly efficient degassing and drying of oils.
Furthermore the built in fine filter (3 µm absolute) removes
contaminating particles.
By lowering the oxygen content (down to 200ppm) and moisture
content (down to 3 ppm) in the transformer oil the ageing
processes (oxidation processes) of the insulation cellulose and
oil are slowed considerably thereby extending the operational
life of the transformer.
The ultimate pressure in the vacuum chamber is 2 mbar. This
pressure is reached when the transformer oil is virtually free of
gases and moisture.
85% of all gases and 75% of the water will be removed from the
oil in one pass. The V30 systems have been installed on
transformers ranging in size from 5000 to 55000 L of oil.